Maintenance
Information Collecting System (MICS)
|
|
|
|
|
This equipment collects, processes and stores Operating
information of substations (e.g. voltage, current, watt-hour, fault
information) and Maintenance information of facilities (monitoring of
equipment condition, equipment error, total number of error counts) at all
once.
Also, It displays the above information on a real time monitor, executes
data processing and makes reports such as daily, monthly and annual
reports.
This System contributes to an immediate collection of required information
and laborsaving at substations because it interactively communicates with
CC (central control center) or Maintenance section through network via
telephone lines.
|
|
|
|
|
|
|
|
|
For DC substations
|
For AC substations
|
Type
|
CM-C
|
Construction
|
Independent Enclosed Panel with
front & back doors
|
Dimensions
of Panel
|
W700D700H2350 (standard)
|
Power
Supply
|
DC 100V and AC 100V, 50Hz/60Hz
|
Display
|
TFT Liquid Crystal Screen (Panel
computer)
|
Operation
|
Touch Panel Operation
|
Input
Ratings
|
AC 110V, 5A, 50Hz/60Hz, DC 4mA -
20mA
|
Numbers of
Inputs
|
AC
|
A/I: 8ch (for 3 phases)
Up to 30 adapters can be connected
|
A/I: 8ch (for 3 phases, single
phase)
Up to 30 adapters can be connected
|
DC Bus
|
A/I: 6ch max.
|
|
DC Feeder
|
A/I: 10ch4 max.
D/I: 10ch4 max.
|
|
AC Bus, AC
Feeder
|
|
A/I: 8ch, D/I: 16ch
Up to 6 adapters can be connected
|
Maintenance
|
A/I: 64ch max. (DC 4mA - 20mA)
D/I: 32ch max.
|
|
|
|
|
|
|
|
|
|
|
|
|
Information
Measuring Equipment
|
|
|
|
|
This equipment collects information of DC bus and
feeders at DC substations. For example, it collects and processes Load
information (voltage, current, watt-hour), Fault information (feeder name,
fault occurrence time, breaking current value, estimated short circuit
current (MEB-5A type)) and Maintenance information. The information is
displayed on a monitor and stored: further, an optional our Play Back
Equipment makes reports of load information (daily and monthly reports),
and displays waveform of fault information and maintenance information as
well. It is also possible to transmit the data to RTU (remote terminal
unit).
In addition, another fault locating type is available, which cooperates
with the Transfer Trip Equipment (refer to DC Equipment for Electric
Railways) and specifies a fault point when a fault occurs at DC feeder
circuit. This is the first type in the industries as with a locating
function.
Japan Patent Nos: 3293759
|
|
|
|
Type
|
MEB-5A
|
MEB-5AL
|
Locating
Function
|
|
|
Construction
|
Panel Mounting Type
|
Power
Supply
|
DC 100V
|
Rating
|
DC 1500V, Feeder: 5kA, Bus: 20kA
|
|
* Locating Function:
|
When a short circuit fault occurs on a
railway track, the fault point shall be calculated using the
distributed ratio of the fault current from both substations.
|
|
|
|
|
|
MEB-5A type
|
|
|
|
|
|
|
|
|
|
|
|
High
Speed Current Transformer
|
|
|
|
|
This is a detector to measure making and breaking
current values and each flowing time of a High speed circuit breaker and
Disconnecting switch installed in substations with high accuracy. This
transformer diagnoses the deteriorating conditions of the High speed
circuit breaker and Disconnecting switch in cooperating with the ME system
control panels at substations.
|
|
|
|
Type
|
CTD-3 (with Auxiliary Box BQ-A13
type )
|
Construction
|
Installing Type
|
Accuracy
|
±1.0%
|
Response
Speed
|
Less than 1ms
|
Power
Supply
|
AC 100V/110V, 50Hz/60Hz
|
Rating
|
Input
|
:
|
10A,
50A, 100A
|
Output
|
:
|
4mA -
20mA (Load: Less than 500)
|
|
|
|
|
|
|
|
CTD-3 type (right : Auxiliary Box BQ-A13 type)
|
|
|
|
|
|
|
|
|
|
|
|
Lightning
Arrester Leakage Current Detecting Equipment
|
|
|
|
|
At substations, lightning arresters are installed
to prevent lightning damage. This equipment is a detector that continuously
monitors leakage current of the arrestor and used to diagnose the
deteriorating conditions of the arrestor in cooperating with ME system
control panels at substations.
|
|
|
|
Type
|
DE-2A
|
Construction
|
Installing Type (Outdoor use)
|
Accuracy
|
±5%
|
Power
Supply
|
AC 100V, 50Hz/60Hz
|
Rating
|
AC 0.5mA
|
|
|
|
|
|
|
DE-2A type
|
|
|
|
|
|
|
|
|
|
|
|
Hall
Generator Type Current Detector
|
|
|
|
|
This detector outputs the current and voltage in
proportion to DC current by using Hall generator (Hall element). The
response speed is so high (less than 1ms) that this detector is ideal for
measuring fault waveform at DC feeder circuit.
|
|
|
|
Type
|
HF-20D
|
Construction
|
Installing Type (divided at
installation)
|
Accuracy
|
Class 1.5
|
Power
Supply
|
AC 100V/200V, 50Hz/60Hz
|
Rating
|
Input
|
:
|
DC
±20kA
|
Output
|
:
|
DC ±5V,
±10V (Burden: More than 3k)
DC ±10mA (Burden: Less than 800)
DC ±20mA (Burden: Less than 400)
|
|
|
|
|
|
|
|
HF-20D type
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This Current Transformer uses an AC power supply and
transforms DC current into the proportionate AC current (saturable
reactor). This is used to measure the insulation of DC current.
Japan Patent Nos: 680292, 680293
|
|
|
|
Type
|
CTB, CTF
|
Construction
|
Installing Type (Indoor or Outdoor
use)
|
Accuracy
|
Class 1.0
|
Power
Supply
|
AC 100V/200V, 50Hz/60Hz
|
Rating
|
For One
direction
|
:
|
3kA, 5kA,
7.5kA, 10kA, 15kA and more
|
For
Both directions
|
:
|
±3kA,
±5kA, ±7.5kA, ±10kA, ±15kA, and more
|
|
|
|
|
|
|
|
CTB type
|
|
|
|
|
|
|
|
|
This Potential Transformer uses an AC power supply
and transforms DC voltage into the proportionate AC current (saturable
reactor). This is used to measure the insulation of DC voltage.
|
|
|
|
Type
|
PTF-H
|
Construction
|
Installing Type (with Multiplier)
|
Accuracy
|
Class 1.0
|
Power
Supply
|
AC 100V/200V, 50Hz/60Hz
|
Rating
|
600V, 750V, 1500V
|
|
|
|
|
|
|
PTF-H type
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This Isolator converts DC voltage or DC current
into insulated output signals. In case the input is high voltage or huge
current, a Divider or a Shunt should be used with.
|
|
|
|
Type
|
IA, IN, IC, IW series
|
Construction
|
Installing Type
|
Accuracy
|
Linearity: ±0.2%
|
Withstand
Voltage
|
AC 2500V, 5500V for 1minute
|
Power
Supply
|
AC 100V/200V, 50Hz/60Hz
|
Rating
|
Input
|
:
|
±50mV
to ±150V, ±1mA to ±100mA
|
Output
|
:
|
±10mA, ±10V,
4mA to 20mA and more
|
|
|
|
|
|
|
|
IN type
|
|
|
|
|
|
|
|
|
|
|
|
DC
Indicating Instrument and Recording Instrument
|
|
|
|
|
a. DC Voltmeter
b. DC Ammeter
c. DC Demand Ammeter
d. DC Recording Voltmeter
e. DC Recording Ammeter
|
|
|
|
|
|
|
|
|
|
|
DC
Integrating Instrument
|
|
|
|
|
a. DC Ampere-hour Meter
b. DC Watt-hour Meter
c. DC Watt-hour Meter for Positive and Negative
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
a. Field Tester for Fault Selective
Equipment for DC Feeder
This tester is used for the characteristic test of fault selective
equipment after the installation. To perform the test, flow the equivalent
current to the test coil of a Fault Detector (used together with the fault
selective equipment).
Type
|
FT-28 and more
|
Construction
|
Carrier Type
|
Accuracy
|
±2.5%
|
Power
Supply
|
DC 100V
|
Rating
|
5A (for less than 4000A) and more
|
|
* Utility model No: H6-57034 (under filing
application)
|
|
|
|
|
b. Field Tester for Fault Selective
Relay for AC Feeder
This tester is used for the fundamental wave characteristic test of fault
selective relay for AC feeder. To perform the test, impress the voltage
that is equivalent to the input current of relay.
Type
|
FT-12
|
Construction
|
Carrier Type
|
Power Supply
|
AC 100V, 50Hz/60Hz
|
|
|
|
|
|
c. Polarity Checker
This checker is used for the polarity checking of transformers for
instruments. You can comprehensively check the polarity of the primary side
of transformers to input terminals of relays without opening the circuit.
Type
|
KS-1D
|
Construction
|
Carrier Type
|
Power
Supply
|
AC 100V or DC 6V (built-in battery)
|
|
|
|
|
|
d. Field Tester for Fault Locator
This tester is used for the individual test of Measuring Unit of Fault
Locator. To perform the characteristic test, supply a simulating input to
the measuring unit from this tester.
Type
|
TLA-1
|
TLX-4
|
Application
|
For AT system AC feeder circuit
|
For BT system AC feeder circuit
|
Construction
|
Carrier Type
|
Carrier Type
(Consists of Power Supply Unit and Reactance Unit)
|
Output
Current
|
35A
|
20A
|
Reactance
Unit
|
|
35(10 taps)
|
Power
Supply
|
AC 100V, 50Hz/60Hz
|
|
|
|